1330 Series

2 Way Solenoid Valves – Combustible gas and other gases

Main Characteristic

Normally Closed and Normally Open
Direct Acting. No minimum differential pressure to operate
or Pilot Operated with extremely low min pressure to open.
High Flow designs
Aluminum Body
1/2″ to 2″ NPT (BSP  upon request)
Coil: Encapsulated Class H 356F with DIN Connectors or flying leads (upon request)
Fast (standard) or slow opening (adjustable)

Applications:

Low and Medium pressure combustion equipment
Low and medium pressure air or any other gas
Complies with regulations and recommendations for use of natural gas
and the combustible gases.
Gas burners
Heating systems
Vacuum
UL certified Shut off Valve

Options:

Explosion Proof
Weather Proof
Manual Operator
Closed Valve Verification Switch

Options Prefix Suffix Examples
Weather Proof Coil YC YC1330LA04T
Explosion & Weather Proof Coil ZC ZC1330LA04T
Closed Valve Verification Switch -I2 1330LA04T-I2
BSP Connections no T 1330LA04T
Energized Coil Indicator Light please ask
INSTALLATION

The preferred installation position is on a horizontal pipe with the coil upright, however you can install the valve in any position.
We recommend installing a strainer of <= 50 micron upstream to the valve.

Voltage Watts Resistance (ohms) Amps Inrush Amps Holding
12V/DC 19  7.3 1.6 1.6
24V/DC 19 27 0.8 0.8
110V/DC 19 0.578 0.17 0.17
24V/AC60 13  4 1.9 1.1
120V/AC60 13  92 0.3 0.2
240V/AC60 13  0.38 0.2 0.1

Other voltages available upon request.

GENERAL DIMENSIONS